 |
|
 |
SMUD Customer Service Center (CSC)

Image 1: Sacramento Municipal Utility District (SMUD) Customer Service
Center (CSC) |
Building Design Features
Underfloor
Air Distribution System Characteristics
UFAD
System Performance
|
Building
Use:
The CSC houses SMUD corporate offices as well as a Payment (Call)
Center, the Energy Technology and Education Center, and conference
facilities. The building is designed to accommodate 550 people
Design Team:
| Owner/developer: |
SMUD |
| Architect: |
Williams + Paddon, Roseville, CA
|
| Mechanical design: |
Peters
Engineering
|
| Contractors: |
Hensel
Phelps - Sacramento
|
| Consultants: |
Robert
Bein, William Frost & Associates |
|
Location:
Sacramento, CA
Size:
Four wings, two or four stories connected to a central entry atrium
Total floor area is 19,320 m2 (208,000 ft2)
Construction
Status:
Construction was completed in 1996.
|
Building
Design Features
The
CSC was intended as a showcase of low-energy design featuring an underfloor air
distribution system, a high-efficiency central chiller plant with thermal
energy (cold water) storage, and efficient electric lighting integrated within
a sophisticated daylighting scheme. Exterior
shading devices and interior light shelves contribute to keeping loads low. SMUD management placed a priority on giving employees personal control
over the indoor environment, and this has been achieved by providing ergonomic
workstations, individual task lights, operable windows, adjustable window
coverings and the accessibility of floor diffusers – a key component of the
underfloor air distribution system.
Each
floor of a wing (except the SE wing) is divided into a number of underfloor
plenum zones by partitions in the plenum that form an air dam (i.e., not
tightly sealed). Each zone has a
volume control damper so an AHU can supply more than one zone.
The
interior is largely open plan with only a small number of private offices
located mostly in the perimeter. The
raised floor system consists of 0.61 m x 0.61 m (24 in. x 24 in.) panels and
houses a 0.3 m (12 in.) high plenum. Floor
panels are covered with 0.46 m x 0.46 m (18 in. x 18 in.) carpet tiles glued
down and overlapping the floor panel joints. A modular cubicle and furniture system is used throughout. The ceiling is made up of suspended acoustical panels.
Suspended direct/indirect fluorescent fixtures provide lighting.
Electrical
distribution consists of hard conduits that feed junction boxes (J-box) in the
plenum from a floor electrical closet. Each
floor has one closet that contains electrical and telecommunications main
distribution circuits. From each
J-box, each of 6-8 cubicles are fed by a metal shielded whip to a utility box
mounted on the underside of the desk. This
box contains surge protection switches and connection ports and is served by
two separate circuits, one for computers and the other for small appliances
(i.e., each of the two circuits’ serves 6-8 cubicles). Two printer stations per 10 cubicles are supplied from floor panel
mounted modules. The computer
circuit is isolated back to distribution. Oversized grounds are used for safety. Telecommunication cables are direct wired from main floor distribution
through 1.18 cm (3 in.) grommets mounted in the floor panels to cubicle
appliances.
Top
Underfloor Air Distribution (UFAD) System Characteristics
Design
Intent
The
decision to use a raised floor for cable management and HVAC in the office area
was the result of a cost-effectiveness analysis that identified first cost
offsets by eliminating overhead ductwork and diffusers and labor savings during
future office reconfigurations. The
potential beneficial effects on employee productivity were discussed but not
quantified. The UFAD system was a
key element for realizing the combination of low energy use and occupant
personal comfort control.
Design/Configuration
| Plenum
Height: |
0.3
m (12 in.) |
| Diffuser
Types: |
Swirl
diffusers supplied by Krantz are used in all UFAD conditioned areas. |
| Raised
Floor: |
0.61
m (24 in.) concrete-core panels using a stringer-less post mounting
system supplied by Tate |
Supply
Air
Temperature: |
Nominal
17°C (63°F), varies with load |
UFAD
System
Types: |
Interior
areas only: Constant air volume, variable temperature system (CAV-VT). |

As
indicated by Figure 2, the SMUD CSC building contains a number of different
roof mounted penthouse AHUs that serve both constant volume and variable volume
(VAV) system types. Perimeter
zones are served by dual duct VAV systems with air supplied by linear bar
grills in the window sills as well as by floor diffusers. All UFAD areas are served by air handlers with hydronic heating and
cooling coils and an economizer. Each
AHU is equipped with a variable speed drive to maintain constant pressurization
in the supply ducts. Each
underfloor plenum zone is supplied through a control damper that maintains
constant plenum pressure. Variable
temperature conditioned air is delivered to the occupied spaces via
occupant-controlled, passive floor diffusers. By design, each cubicle is equipped with at least one floor diffuser. Return air grilles are located at ceiling level. The return fan is shared between the interior and perimeter systems.
Operation
Since the
building is equipped with operable windows, the HVAC systems were designed to
maintain slightly positive pressure in the building to ensure exfiltration;
thus only filtered, conditioned air is supplied to the occupied space. The operable windows are equipped with micro-switch sensors that reset
operation of the adjoining VAV box to night setback mode (i.e., increased
cooling and decreased heating setpoints and minimum volume damper position)
anytime a window is opened.
A
separate dual-duct VAV system, with registers in the window sills, provides the
necessary heating and cooling to accommodate skin loads at the perimeter of the
building when required. The hot
deck of the VAV system is supplied from the return plenum of the office space,
and in mild winter conditions, the warm return air can be used to heat the
perimeter without energizing the heating coil.
For UFAD
systems the supply fan is modulated to control supply duct pressure to 125 Pa
(0.5 in. w.c.). Although the
plenum supply dampers are modulated to maintain constant pressure differential
across the access floor panel, the system from the perspective of the delivery
of room air operates as a CAV-VT system. Variations
in plenum pressure would result only from changes in floor diffuser opening by
the occupants. A fan tracking
system that sets return volume equal to 85% of total supply flow controls the
return fans. As indicated in
Figure 2, each plenum zone is provided with a corresponding room air
temperature sensor (all located on interior spaces; the perimeter system is
controlled from wall sensors located on exterior walls). All zone sensors for
an AHU are used to compute an average space temperature for the AHU. During cooling the SAT is varied from 12.8°C to 21.1°C (55°F to 70°F)
as the deviation of the average from room setpoint varies between –1 to +2°F. During heating the SAT is varied between 35°C and 21°C (95°F and 70°F)
for the same deviation range, respectively.
Top
UFAD System Performance
In a survey
carried out by CBE covering 179 of the 550 employees, nearly 2/3 of respondents
indicated they operate the windows less than once per month. In contrast, 84%
of survey respondents indicated that they have access to an adjustable floor
diffuser, of whom over 60% stated they use these diffusers at least
occasionally. Overall (for both
UFAD and conventional areas) 31% of occupants were dissatisfied with air
movement, and 22% with temperature. These results are in contrast with
information that facility personnel receive via the complaint system and
operational data. This information
shows that very few complaints are received and overall the system performs
with little variation in temperature. They also cite the occupant control
feature and easy relocation of diffusers as key in maintaining acceptable
individual comfort. In general the facility engineers
report that the UFAD system has met the original intentions of low noise,
minimal hot and cold complaints, and better indoor air quality.
Energy
use based on billing information for the building as a whole is shown in Figure
3. Average total energy intensity for the three year period 1997-1999 was 1.48
kWh/m2/year (52,600 Btu/ft2/year); average annual demand
was 416 kW.

CBE
Findings
(These
comments reflect the views of CBE researchers based on a limited study of the
building and do not necessarily represent those of the designers and/or
owners.)
System
design and control - This design represents somewhat of a hybrid: the
perimeter zones are not overhead systems but also are not true UFAD; air is
supplied at variable volume to window sill diffusers along with passive floor
diffusers. Interior zone sensors
control the supply air temperature for the floor diffusers while separate
sensors on perimeter exterior walls control the perimeter system. Thus, the perimeter system augments the cooling supplied by the UFAD
system in these zones. The
interior areas are more typical CAV-VT UFAD systems. It is unclear as to the impact on stratification and comfort of
operating the perimeter zones with VAV sill diffusers.
Problems
related to control have occurred due to the averaging process used to
control the AHU SAT. Using the average for all zones will tend to leave some
zones unsatisfied. However,
occupant adjustment of the floor diffusers should help to accommodate these
variations.
The
operable windows were designed with micro-switches to disable the local VAV
box when the window was opened. However,
these switches were also tied to the alarm system resulting in false alarms. For this reason the window switches have been disconnected.
The windows are not frequently opened primarily because of outside
noise (the CSC is near a freeway).
Economizer
mode – This system uses an outside air economizer (i.e., changeover
controlled by outside temperature alone rather than by return temperature) but
this may not be the most energy efficient solution for this system, especially
with a 21°C (70°F) changeover temperature. Since stratification will cause the return temperature to be
significantly greater than normal the changeover point could be set higher
allowing a greater range of economizer operation. In addition, when the economizer is in wide open mode both return and
outside air dampers are opened 100%; this will most likely result in greater
mixed air temperature than if the return damper was closed.
Occupant
survey - A review of occupant survey data revealed a surprising number of
comments related to dust problems with diffusers, poor location of diffusers,
difficulties with adjustment, and inadequate airflow (too much or too little). Half of the respondents’ (159) who had access to a floor diffuser
submitted comments. The majority (77%) of those comments indicated one or more
of the problems indicated above. However,
of these comments 36% register dissatisfaction with air movement and/or
temperature. This is
approximately consistent with the overall temperature and airflow
dissatisfaction levels; i.e., 24% overall reported temperature dissatisfaction
of some sort and 31% reported air movement dissatisfaction. These results do, however, contrast with views expressed by facility
managers who cite a low number of complaints. One possible explanation is that occupants may not know that the
diffusers are adjustable and/or movable and therefore do not consider filing a
complaint. Many of these issues
appear to be resolvable by simple relocation and/or better diffuser design, or
by improved system control. Facility personnel report that the majority of
complaints are derived from either equipment failures or stuffy conditions
because too many diffusers are turned off.
The
survey results also indicate that 27% of occupants with diffusers never
adjusted them while the remainder changed them from 1-4 times a month (49%)
to more than once per day (5%).
Despite
a 24% dissatisfaction rating for the floor diffusers, 70% of the occupants
with diffusers rated their importance as high vs. only 7% for low
importance. This tends to
corroborate research findings that occupants prefer to have control over
their environment.
Stratification
– Facility engineers report that the system exhibits very little
stratification. This is based on
EMCS data and not measurements in the space. However, the return configuration is complicated by the fact that all
wings open into the central atrium and the return system supports both the
perimeter overhead VAV system as well as underfloor zones. This makes judgments about stratification based on EMCS return air
temperatures difficult. Also, it
is possible that this system is over-aired. The fact that a significant number of diffusers are turned off due to
occupants feeling too cool and the supply air temperature operates in a narrow
range of 65°F and above (even on hot Sacramento days the SAT never is less
than 65°F) suggests that the overall supply volume is too great. High airflow relative to load will decrease stratification. Constant volume systems inevitably will be
over-aired at light load
conditions since the peak volume is being used to support a lower load
condition, which will result in less stratification. This whole situation can sometimes be exacerbated by the difficulty
associated with adjusting the floor diffusers due to sticking and non-linear
airflow performance as the basket damper is adjusted; occupants will sometimes
default to the least disturbing condition and close the damper.
Date
Reviewed: December 1999 - September
2000
Print-friendly version
|
 |