 |
|
 |
Sample Plans and Sections
The use of
partitions to divide the underfloor plenum into separate zones (e.g., interior
and perimeter) is comparable to the conventional approach to zoning with
overhead air distribution systems. It enables supply air of different
temperatures or volumes to be delivered to different spaces within the overall
plan. Diffusers within the same zone typically receive supply air of similar
temperature and pressure.
In addition to being either partitioned or open-plan, plenums can operate as
pressurized or zero-pressure. Pressurized plenums have a small positive static
pressure applied, created by a central fan in the air-handling unit (AHU), that
drives the air up through the diffusers to the lower pressure surroundings of
the conditioned office space. Standard methods of control at the central AHU
are used to maintain the desired overall supply volume and temperature under
thermostatic control, and a pre-set pressure level, at which the diffusers
achieve optimum performance. The low operational pressure of underfloor
plenums, compared to ceiling-based systems, potentially reduces fan energy
consumption and thus operating costs.
In zero-pressure plenums, small local fan units draw air from the underfloor
plenum and deliver it to the space through floor diffusers or outlets located
in the furniture or partitions. Compared to passive diffusers, used with
pressurized-plenum systems, fan-powered outlets are generally more easily and
effectively controlled by nearby occupants. However, for reasons of reduced
maintenance, installation and equipment costs, pressurized-plenums are the most
commonly installed systems at present.
Air is typically extracted from the room through return grilles located at
ceiling level using a conventional ceiling-return plenum. If no plenum is
present, air can be returned through high side-wall grilles. The return air is
then ducted back to the AHU where it is either exhausted to the outdoors, or
filtered and dehumidified as necessary in the AHU before mixing with the supply
air and re-entering the underfloor plenum. In some configurations, a portion of
the return air is re-circulated directly back into the underfloor plenum where
it is thoroughly mixed with incoming primary air from the AHU.
Some portion of each floor in a typical building will be devoted to
accommodating the mechanical plant risers, equipment (e.g. the AHU) and
circulation shafts such as stairs and elevators. In the plans indicated this
area is placed as centralized at the core of the floor plate, however this is
not always the case. Other possibilities include a distributed or perimeter
service area, for example.
Configuration Examples
Shown below, in plan view and corresponding floor-to-floor section, are three
different pressurized-plenum configurations. The first two examples represent
earlier UFAD designs in which the more extensive use of ductwork and partitions
within the plenum was a more common practice. It is now recommended to
minimize to the extent possible, the amount of installed ducts, air highways,
and other HVAC-related components in the underfloor plenum so that it can serve
as a highly flexible and accessible service plenum. For any particular building
project, the most suitable configuration will be determined by a number of
parameters unique to that project - such as floor plate area, site-specific
climate, or anticipated HVAC loads and their distribution, for example. For
this reason it is important that decisions as to the plenum configuration be
made with respect to the project's characteristics. In addition, please note
that the drawings shown below represent only three of any number of possible
underfloor plenum designs.
- Multi-zoned with
extensive perimeter ductwork
- Multi-zoned with
limited perimeter ductwork
- Open-plan plenum
1. Multi-zoned with extensive perimeter ductwork
This approach has been used in many existing underfloor installations and
uses a similar control strategy to overhead variable-air-volume (VAV) systems.
Conditioned air is supplied to interior and perimeter zones through an
underfloor supply duct encircling the interior/perimeter boundary. In addition
to defining the interior and perimeter, underfloor sheet metal partitioning is
used to create smaller zones around the perimeter of the floor plan, as well as
other zones as necessary. Using a conventional variable-air-volume (VAV)
control strategy, air flow to each zone is controlled by VAV terminal units in
response to zone thermostats. Supply air is delivered to all zones through
passive (swirl or other non fan-powered) diffusers. Nearby occupants have some
amount of control over these floor diffusers. In this example, heating in the
perimeter zones is accomplished with reheat coils (electric or water-based) in
the terminal units. The large amount of perimeter ductwork may restrict the
flexibility to reconfigure plenum services in the future.
 
Top of Page
2. Multi-zoned, limited perimeter ductwork
This approach also uses underfloor partitioning to divide interior and
perimeter zones. However, the amount of underfloor ductwork is reduced by
relying on a single feeder duct to supply conditioned air to each of the four
large perimeter zones, as shown. Standard methods of control at the central AHU
are used to deliver a constant volume, variable temperature supply of air to
the interior zone. Air flow from individual diffusers in the interior zone may
be controlled by nearby occupants. Air flow to the
perimeter zones is delivered through linear grills and controlled by VAV
terminal units in response to zone thermostats. Perimeter finned tube heating
coils, located directly under the linear grills in the underfloor plenum, are
used during the heating mode.
 
Top of Page
3. Open-plan
plenum
Conditioned air from a central source is distributed to diffusers across the
entire floor area through a single, undivided pressurized plenum. Standard
methods of control at the central AHU are used to maintain the static pressure
in the plenum at a constant level. Supply air is delivered to the interior zone
through passive diffusers that can be controlled by nearby occupants. During
cooling mode in the perimeter zone, supply volume through the diffusers is
automatically controlled in response to zone thermostats. During heating mode,
a fan coil unit is activated, drawing inlet air through ducts from designated
floor diffusers, and discharging the supply air through ducted diffusers near
the building facade. These inlet and discharge diffusers are typically closed
off to the underfloor plenum to isolate the heating operation from the cooler
plenum air. When called for by the zone thermostat, a reheat coil in the fan
coil unit provides additional heating capacity.

Print-friendly
version
|
 |