 |
Back
to web version
Sample Plans and
Sections
The use of partitions to
divide the underfloor plenum into separate zones (e.g., interior and perimeter)
is comparable to the conventional approach to zoning with overhead air
distribution systems. It enables supply air of different temperatures or
volumes to be delivered to different spaces within the overall plan. Diffusers
within the same zone typically receive supply air of similar temperature and
pressure.
In addition to being either partitioned or open-plan, plenums can operate as
pressurized or zero-pressure. Pressurized plenums have a small positive static
pressure applied, created by a central fan in the air-handling unit (AHU), that
drives the air up through the diffusers to the lower pressure surroundings of
the conditioned office space. Standard methods of control at the central AHU
are used to maintain the desired overall supply volume and temperature under
thermostatic control, and a pre-set pressure level, at which the diffusers
achieve optimum performance. The low operational pressure of underfloor
plenums, compared to ceiling-based systems, potentially reduces fan energy
consumption and thus operating costs.
In zero-pressure plenums, small local fan units draw air from the underfloor
plenum and deliver it to the space through floor diffusers or outlets located
in the furniture or partitions. Compared to passive diffusers, used with
pressurized-plenum systems, fan-powered outlets are generally more easily and
effectively controlled by nearby occupants. However, for reasons of reduced
maintenance, installation and equipment costs, pressurized-plenums are the most
commonly installed systems at present.
Air is typically extracted from the room through return grilles located at
ceiling level using a conventional ceiling-return plenum. If no plenum is
present, air can be returned through high side-wall grilles. The return air is
then ducted back to the AHU where it is either exhausted to the outdoors, or
filtered and dehumidified as necessary in the AHU before mixing with the supply
air and re-entering the underfloor plenum. In some configurations, a portion of
the return air is re-circulated directly back into the underfloor plenum where
it is thoroughly mixed with incoming primary air from the AHU.
Some portion of each floor in a typical building will be devoted to
accommodating the mechanical plant risers, equipment (e.g. the AHU) and
circulation shafts such as stairs and elevators. In the plans indicated this
area is placed as centralized at the core of the floor plate, however this is
not always the case. Other possibilities include a distributed or perimeter
service area, for example.
Configuration
Examples
Shown below, in plan view and corresponding floor-to-floor section, are three
different pressurized-plenum configurations. The first two examples represent
earlier UFAD designs in which the more extensive use of ductwork and partitions
within the plenum was a more common practice. It is now recommended to
minimize to the extent possible, the amount of installed ducts, air highways,
and other HVAC-related components in the underfloor plenum so that it can serve
as a highly flexible and accessible service plenum. For any particular
building project, the most suitable configuration will be determined by a
number of parameters unique to that project - such as floor plate area,
site-specific climate, or anticipated HVAC loads and their distribution, for
example. For this reason it is important that decisions as to the plenum
configuration be made with respect to the project's characteristics. In
addition, please note that the drawings shown below represent only three of any
number of possible underfloor plenum designs.
- Multi-zoned
with extensive perimeter ductwork
- Multi-zoned
with limited perimeter ductwork
- Open-plan
plenum
1. Multi-zoned with
extensive perimeter ductwork
This approach has been used
in many existing underfloor installations and uses a similar control strategy
to overhead variable-air-volume (VAV) systems. Conditioned air is supplied to
interior and perimeter zones through an underfloor supply duct encircling the
interior/perimeter boundary. In addition to defining the interior and
perimeter, underfloor sheet metal partitioning is used to create smaller zones
around the perimeter of the floor plan, as well as other zones as necessary.
Using a conventional variable-air-volume (VAV) control strategy, air flow to
each zone is controlled by VAV terminal units in response to zone thermostats.
Supply air is delivered to all zones through passive (swirl or other non
fan-powered) diffusers. Nearby occupants have some amount of control over these
floor diffusers. In this example, heating in the perimeter zones is
accomplished with reheat coils (electric or water-based) in the terminal units.
The large amount of perimeter ductwork may restrict the flexibility to
reconfigure plenum services in the future.


Top of Page
2. Multi-zoned,
limited perimeter ductwork
This approach also uses
underfloor partitioning to divide interior and perimeter zones. However, the
amount of underfloor ductwork is reduced by relying on a single feeder duct to
supply conditioned air to each of the four large perimeter zones, as shown.
Standard methods of control at the central AHU are used to deliver a constant
volume, variable temperature supply of air to the interior zone. Air flow from
individual diffusers in the interior zone may be controlled by nearby
occupants. Air flow to the perimeter zones is
delivered through linear grills and controlled by VAV terminal units in
response to zone thermostats. Perimeter finned tube heating coils, located
directly under the linear grills in the underfloor plenum, are used during the
heating mode.


Top of Page
3. Open-plan
plenum
Conditioned air from a
central source is distributed to diffusers across the entire floor area through
a single, undivided pressurized plenum. Standard methods of control at the
central AHU are used to maintain the static pressure in the plenum at a
constant level. Supply air is delivered to the interior zone through passive
diffusers that can be controlled by nearby occupants. During cooling mode in
the perimeter zone, supply volume through the diffusers is automatically
controlled in response to zone thermostats. During heating mode, a fan coil
unit is activated, drawing inlet air through ducts from designated floor
diffusers, and discharging the supply air through ducted diffusers near the
building facade. These inlet and discharge diffusers are typically closed off
to the underfloor plenum to isolate the heating operation from the cooler
plenum air. When called for by the zone thermostat, a reheat coil in the fan
coil unit provides additional heating capacity.

|
 |